Description

EGL33 ups gruppi di continuità trifase doppia conversione sinusoidali

 

EGL 33 is available in capacities from 10 KVA to 30 KVA, with on-line double conversion and digital control technology.

Because of its versatility it is suitable to supply any electrical and electronic system in critical situations; it is possible to use the product as a frequency converter 50 / 60Hz or with the use of motor current generators

UPS DOUBLE CONVERSION
A real DOUBLE CONVERSION UPS which will provide a perfect power, for complete protection of high quality for your sensitive devices, such as PC Networks (Network), Small computer centers, Server, Telecommunications, Sanitary appliances / hospital, and general industrial applications

POWER FACTOR IN OUTPUT φ 0.8
Comparing this line UPS ON-LINE with the competition on the market today, we can say that they have the best output power factor: 0.8. They offer high performance and efficiency for critical applications

WIDE RANGE INPUT (200 V -500 V)
EGL33 is able to provide stable and clean power to the connected equipment even in very critical and unstable environments.

FREQUENCY CONVERTER 50/60 Hz FUNCTION
Lock output frequency at 50Hz or 60Hz regardless of input frequency and eliminates the By-Pass

FUNCTION (EPO) Emergency Power Off
This function serves for a UPS shutdown by the personnel in case of fire and other emergency situation.

OPERATION OF CONTEMPORARY SNMP + USB + RS-232
This feature allows you to use communication to all USB ports, RS-232 and SNMP simultaneously.

BATTERY CHARGER DESIGNED TO OPTIMIZE THE PERFORMANCE OF THE BATTERY
The EGL33 series is equipped by a battery charger at 3 steps, to optimize battery performance. This feature prolongs the autonomy and optimizes battery recharge time also the extension of the battery charger is essential for recharging of batteries with higher power used to achieve longer ranges.

BY-PASS FOR MAINTENANCE
The By-Pass Manual ensures the lack of voltage inside the UPS for maintenance, ensuring supply to the equipment connected downstream.

OPERATION PARALLEL redundant
The EGL33, can work in parallel redundant up to 3 units; This increases the power capacity and the safety of work without interruption of the service

POWER FACTOR CORRECTION ON ALL STAGES
PFC improves the quality of the current consumption and increases the energy efficiency, with the consequent economic savings

COMMUNICATION
Software for all operating systems and network environments. supervision and shutdown platform

GUARANTEE 24 MONTHS

gruppi statici di continuità trifase on line doppia conversione

 

 MODEL EGL3310k (s) EGL3320k (s) EGL3330k (s)
 Rated power 10kVA/8kW 20kVA/16kW 30kVA/24kW
 INPUT
 Rated voltage 400Vac +N + PE three phase
 Low voltage transfer 176Vac @ 100% load (Vph) / 110Vac @ 50% load (Vph)
 Low voltage return to network 186Vac @ 100% load (Vph) / 120Vac @ 50% load (Vph)
 High voltage transfer 300Vac ±3% (Vph)
 High voltage return to network 290Vac ±3% (Vph)
 Frequency from 46 to 54Hz @ 50Hz / 56-64 Hz @ 60Hz
 No. of phases three phase + N + PE
 Power factor > 0.99 @ 100% load
 THDi

<6% @ 100% load

 OUTPUT
 Rated voltage 360-380-400-415Vac three phase + N + PE
 Output accuracy ± 1%
 Inverter frequency 50 ± 0.1 Hz or 60Hz ± 0.1Hz
 Crest factor 3 : 1
 Harmonic distortion < 2% THD (linear load) < 5% THD (non linear load)
 AC/DC line/battery transfer time zero
 Inverter/by-pass transfer time zero
 Wave form Pure Sine Wave
 Efficiency 89-90% (line) 86-89% (inverter)
 BATTERIES
 No. of batteries/voltage/rating 20 x 12V / 9 Ah 2×20 x 12V / 9 Ah 3×20 x 12V / 9 Ah
 Charging current 1.0A 2.0A 4.0 A
 Typical charge time 9 h 90% capacity
 Charging voltage 273Vdc ± 1%
 Charging current models (S) 4.0A 4.0A 12.0A
 PROTECTIONS
 Display UPS state, charge level /battery level / in/out voltage / battery discharge time / fault
 Inverter mode beep every 4″
 Exhausted battery beep every 1″
 Overload two beeps per seconds
 Fault continuous beep
 OTHER DATA
 Humidity 0-90% without condensation (0°C – 40°C)
 Noise 60 dBA at 1 m. <65 dBA at 1 m.
 Dimensions mm. 815x250x826 815x300x1000
 Net weight kg. 109 164 234
 Dimensions mm. model (S) 592x250x576 815x250x826
 Net weight kg. 38 40 64
 interface RS-232 / USB Management software compatible with Windows, Novell, Linux, FreeBSD
 SNMP (optional) Power management from SNMP Manager and web browser