TE – SINGLE PHASE ISOLATION AND SAFETY TRANSFORMERS from 50VA to 3000VA

Category,

SINGLE PHASE ISOLATION AND SAFETY TRANSFORMERS from 50VA to 3000VA

Standard input voltage range 220-230-240-380-400-415V
Open type contruction
IP00 protection degree
Isolation class E (AT max 40°C)
Frequency 50/60Hz
Separated copper windings cl. F-H
Resin impregnated and tropicalized
Protected terminals
Earth connection
Standards applied: EN61558-2-4 / EN61558-2-6
Copper earthed screen between windings available on request. Add “S” at the end of code
Last three digits correspond to the input/output voltage combination.
scheme of 12-24V isolation transformerscheme of 55-110V isolation transformer symbol of safety transformersymbol of isolation transformersim-ce
output voltage last 3 digits code     drawing of safety isolation transformer
12-24V 001
24-48V 002
55-110V 003
110-220V 004
power
VA
part no. losses
W
Imp. V
%
dimensions mm. weight
kg
box
a b c d e f
50 TE009… 7 11 77 90 75 56 47 4 1.1 MB01
100 TE029… 15 8.5 86 100 82 63 55 5 2.2 MB01
200 TE059… 21 5.8 98 110 90 78 70 5 3.5 MB02
300 TE079… 26 4.6 122 110 112 90 76 6 4.5 MB03
500 TE119… 46 4.5 122 120 112 90 86 6 6.0 MB03
750 TE169… 55 3.9 152 120 145 125 93 6 8.9 MB04
1000 TE179… 58 3.9 152 110 140 125 103 6 8.9 MB04
1500 TE199… 77 3.7  152 120 140 125 113 6 12.5 MB04
2000 TE219… 93 3.5 184 120 170 150 122 8 18.0 MB05
3000 TE249… 120 3.5 194 130 180 160 125 8 21.2 MB06
power VA Instant. power VA efficiency voltage regulation
cos-phi=0.5 cos-phi=0.3 cos-phi=1 cos-phi=0.45 cos-phi=1 cos-phi=0.45
50 85 125 0.80 0.61 6.6 2.6
100 230 310 .84 .71 5.2 2.3
200 590 830 0.85 0.73 4.5 2.2
300 745 910 0.88 0.77 5.3 2.8
500 1180 1500 0.91 0.82 4.1 2.2
750 2002 2680 0.93 0.84 3.1 2.0
1000 2690 3390 0.93 0.94 2.5 1.5
1500 4040 4980 0.94 0.87 1.7 1.5
2000 5600 6400 0.95 0.88 1.7 1.5
3000 9400 11600 0.95 0.87 1.7 1.5