ITA – SINGLE PHASE SEPARATION AND CONTROL TRANSFORMERS from 50VA to 3000VA

Category,

SINGLE PHASE SEPARATION AND CONTROL TRANSFORMERS from 50VA to 3000VA

Standard input voltage 230-400V
Open type construction
IP00 protection degree
Isolation class E (AT max 40°C)
Frequency 50/60Hz
Separated copper windings cl. F-H
Resin impregnated and tropicalized
Protected terminal blocks
Earth terminal
Applied standards: EN61558-2-2
Last 3 digits of the code correspond to input/output voltage combination
sch-ita sim-cesim-tracom
output voltage last 3 digits code    di-t246punlato
12-24V 001
24-48V 002
55-110V 003
110-220V 004
power
VA
part no. losses
W
Imp.V
%
dimensions mm. weight
kg
box
a b c d e f
50 ITA009… 7 11 77 60 72 62 48 4 1.1 MB01
100 ITA029… 15 8.5 87 65 80 71 53 5 1.7 MB01
200 ITA059… 21 5.8 98 80 90 82 70 5 3.2 MB02
300 ITA079… 26 4.6 125 80 120 99 64 6 4.5 MB03
500 ITA119… 46 4.5 125 100 120 100 84 6 5.9 MB03
750 ITA169… 55 3.9 152 100 145 125 93 6 8.9 MB04
1000 ITA179… 58 3.9 152 110 140 125 103 6 8.9 MB04
1500 ITA199… 77 3.7  152 120 140 125 113 6 12.5 MB04
2000 ITA219… 93 3.5 184 120 170 150 122 8 18.0 MB05
3000 ITA249… 120 3.5 194 130 180 160 125 8 21.2 MB06
power VA Instant. power VA efficiency voltage regulation
cos-phi=0.5 cos-phi=0.3 cos-phi=1 cos-phi=0.45 cos-phi=1 cos-phi=0.45
50 85 125 0.80 0.61 6.6 2.6
100 230 310 .84 .71 5.2 2.3
200 590 830 0.85 0.73 4.5 2.2
300 745 910 0.88 0.77 5.3 2.8
500 1180 1500 0.91 0.82 4.1 2.2
750 2002 2680 0.93 0.84 3.1 2.0
1000 2690 3390 0.93 0.94 2.5 1.5
1500 4040 4980 0.94 0.87 1.7 1.5
2000 5600 6400 0.95 0.88 1.7 1.5
3000 9400 11600 0.95 0.87 1.7 1.5