ABP33 – THREE PHASE ADJUSTABLE AC POWER SOURCE from 1KVA to 2000kVA 0:260V/0:520V adjustable – 40:500Hz adjustable
THREE PHASE ADJUSTABLE AC POWER SOURCE from 1KVA to 2000kVA 0:260V/0:520V adjustable – 40:500Hz adjustable
DESCRIPTION OF THE FREQUENCY CONVERTER
The ABP Series K-FACTOR Solid State/Static Frequency Converter is one of the most popular AC power supplies designed to change AC power from 50Hz to 60Hz or 60Hz to 50Hz, or convert traditional 50/60 Herts to any frequency between 40Hz and 500Hz, like 400Hz or convert 50/60Hz to 16.67Hz / 25Hz / 100Hz (on request), with adjustable output voltage from 0V to 520Vac
APPLICATIONS
Frequency converters can be used for various applications, from test benches and lines to carry out tests on electrical and electronic equipment (motors, resistors, solenoid valves, etc.), to research and development laboratories to generate different voltages and frequencies with maximum freedom by simulating foreign electricity networks different from the national one or anomalies and unforeseen situations, up to industrial production lines, where stability is required due to repetitive variations on the network, high voltage peaks and/or voltage drops (brownout) more absolute. For the equipment, equipped with a special transformer, total immunity of the load from any disturbances coming from and passing through the main distribution network is ensured.
ELECTRONIC VOLTAGE VARIATOR
Comparable to a traditional motorized voltage stabilizer – booster, through an electronic circuit it reproduces the voltage supplied, and in a very rapid intervention time (< 1 mS), even in the event of a change in the load or voltage of the input network, it ensures the power supply to the connected users. It is possible to prepare the regulation and/or setting of the output voltage both from the front panel and from the RS232 serial input with Modbus protocol.
FREQUENCY CONVERTER
This frequency converter allows the supply of a voltage with a different frequency than that of the power supply line, with a perfectly sinusoidal wave shape. The frequency can always be adjusted, for any voltage value set, from 40Hz up to 500Hz.
ELECTRONIC STABILIZER
Equipped with a standard isolation transformer, it constantly ensures the values of the supplied and set voltage, even if higher than the input voltage.
SYSTEM ADVANTAGES
WHY GET A POWER SUPPLY ADJUSTABLE IN FREQUENCY AND AC VOLTAGE?
Dimensions and weights significantly smaller than a rotary converter, therefore better handling.
Absence of moving mechanical parts, therefore no wear or need for maintenance and consequently no operating costs.
Greater efficiency, which translates into lower energy consumption.
Dynamic response speed (< 1 mS), consequently better performance and greater protection of the connected load.
High precision in stabilization.
Elimination of impurities from the power supply network (the voltage supplied is generated by a DC), to the benefit of the protection and performance of the connected equipment.
Output frequency range: 40 to 500Hz Output voltage range: 0:150Vac and 0:300Vac
Output waveform: perfectly sinusoidal
Output VOLTAGE accuracy: ± 1%.
Harmonic distortion with linear load: < 3%
Output frequency accuracy: ± 0.01%
The product automatically changes the output range, delivering from 0 to 150Vac a current double the maximum current of the voltage range up to 300Vac, referred to 230V. This means that full power will always be available even with 115Vac output.
The distortion of the output waveform with the loads applied as indicated by CEI EN 50091 fully complies with the Regulations.
Electronic protections:
For overloads between 101% and 200% of the nominal current the converter powers the load for 5″, beyond which it disables the output
In the event of a short circuit, the output is immediately disabled.
It is possible to set a maximum voltage or maximum current protection that can be delivered to avoid unwanted damage to the equipment under test
Automation functions:
It is possible to store and then recall up to 32 settings of voltage – frequency – power time combinations to facilitate the testing settings by an operator.
It is possible to memorize and then activate complex test cycles by inserting up to 128 memory sets into the test cycle which represent a combination of voltage – frequency – ramp time – power supply duration, in this way it is possible to repetitively simulate a sequence of different power conditions by simulating numerous regular or abnormal conditions, including blackouts or voltage spikes.
All functions can be controlled remotely via RS232 (rs485 on request); via the 5V trigger it is possible to start data collection when the load is powered.
NEW 2024/2025!
THE NEW REMOTE MANAGEMENT SOFTWARE OF THE ABP SYSTEM FROM WINDOWS PC IS AVAILABLE, with complete management of output voltages and frequencies, reading and recording of test data on XLS files, management of an infinite number of test cycles, each with max 128 combinations of voltage, frequency and duration of the test step, for complete automation of tests even in the presence of numerous different types of operation (optional).
| Rated power |
1kVA, 3kVA, 6kVA, 9kVA, 15kVA, 20kVA, 30kVA, 45kVA, 60kVA, 100kVA, 150kVA, 200kVA, 300kVA, 400kVA, 500kVA ~ 2000kVA (Select a rating) |
| Input | |
| Three phase | 400/230Vac ±10%alternative input voltage on request: 208/120Vac ±10%, 220/127Vac ±10%, 380/220Vac ±10%, 415/240Vac ±10%, 440/254Vac ±10%, 480/277Vac ±5% |
| Frequency | 50Hz/60Hz ±5%, 400Hz (optional) |
| Power factor | ≥ 0,8 (standard type) |
| ≥ 0,9 (optional, 12 pulse) | |
| Output | |
| Three phase | 230/400Vac ±10%alternative output voltage on request: 120/208Vac ±10%, 127/220Vac ±10%, 220/380Vac ±10%, 240/415Vac ±10%, 254/440Vac ±10%, 277/480Vac ±5% |
| Frequency | 40-500Hz adjustable
alternative output frequency on request: 50Hz, 60Hz, 100Hz, 200Hz, 45-200Hz adjustable, 400Hz, 40Hz ~ 500Hz regolabile, 16.67Hz, 25Hz, 400-1000Hz |
| Voltage accuracy | ≤ ±1% FS (Full Scale) |
| Frequency accuracy | ≤ ±0,01% FS (Full scale) |
| Total Harmonic distortion | THD ≤ 3% @ linear load, sine wave output
THD ≥ 5 ≤ 10% @ non linear load, sine wave output |
| Crest Factor | 3:1 |
| Overload | Continuous load 100%, ≤110% – 15 minutes, ≤125% – 10 minutes
≤150% – 1 minute, ≤200% – 5 seconds >200% immediate cut-off |
| Interface | RS232C/RS485/GPIB |
| Protections | Overload, overvoltage, overtemperature, short circuit,
Alarms and display message |
| IP Protection | IP22 (standard), IP32 / IP54 (optional) or according to request |
| LCD Display | Digital frequency meter |
| Digital voltmeter | |
| Digital current meter | |
| Digital power /power factor meter | |
| Environmental conditions | |
| Temperature | operating: -10 °C ~ 55 °C |
| ambient: -10 °C ~ 45 °C | |
| Audible noise | ≤ 65dB at 1 m |
| Humidity | 10 ~ 90% without condensation |
| Altitude | ≤ 1800m |
| Reliability and efficiency | |
| MTBF | 50.000 h |
| MTTR | < 30 min |
| Total efficiency | ≥ 85% |
| Standards | EN50054-95, EN 50150-1991, EN 50150-2006, EN 50171-1992, GBT 2008/5465,2, GB/T 16935.5-2008, GB/T 16935.4-2011 |
| Product code | Power
KVA |
input | Output | Dimensions
(W×D×H) mm |
Net weight
(Kg) |
| ABP33001 (ABP13001) | 1 | THREE PHASE
(or single phase) |
THREE PHASE | 430 (485)x550x222 | 45 |
| ABP33003 (ABP13003) | 3 | THREE PHASE
(or single phase) |
THREE PHASE | 430 (485)x550x430 | 62 |
| ABP33006 | 6 | THREE PHASE | THREE PHASE | 430 (485)x650x600 | 92 |
| ABP33009 | 9 | THREE PHASE | THREE PHASE | 430 (485)x650x600 | 121 |
| ABP33015 | 15 | THREE PHASE | THREE PHASE | 550x700x800 | 155 |
| ABP33020 | 20 | THREE PHASE | THREE PHASE | 550x900x1000 | 175 |
| ABP33030 | 30 | THREE PHASE | THREE PHASE | 550x900x1000 | 290 |
| ABP33045 | 45 | THREE PHASE | THREE PHASE | 550x1000x1300 | 440 |
| ABP33060 | 60 | THREE PHASE | THREE PHASE | 550x1000x1300 | 470 |
| ABP33100 | 100 | THREE PHASE | THREE PHASE | 1050x700x1550 | 600 |
| ABP33150 | 150 | THREE PHASE | THREE PHASE | 1250x880x1450 | 780 |
Download the testingsolution software presentation here.