NTL – MODULAR UPS THREE PHASE, DOUBLE CONVERSION, SINE WAVE, RACK MODULES form 50 to 600KVA

The new NTL range uses the modular 19″ rack drawer technology and was created to guarantee the best quality and reliability of service.

Each power module works in a “decentralized parallel” with the others, and the complete system autonomously divides the input load.

In the event of a failure of one of the modules, it is automatically excluded (decentralized parallel), thus ensuring a seamless power supply with the remaining modules.

Among the strengths of the NTL modular range we have a system efficiency > 95% (high efficiency), a reduction in repair times and service costs of less than 30 ‘and the centralization of the static switching system that gives greater guarantees.

We recommend the use of the NTL series for Data Centers, Banks, Hospitals, Airports, Emergency Lights

and any Industrial application.

Display LCD touch screen

MAIN FEATURES

  • Input power factor 0.99
  • Harmonic input distortion <2%
  • Centralized control display, which allows you to check at any time, (even by removing a single module) the actual power and data related to all modules.
  • EPO function
  • Display LCD touch screen

COMMUNICATION PORTS:

  • 1x RS232 – 2x Rs485
  • 1x MODBUS PORT
  • 1x CLEAN CONTACTS
  • 2x COMMUNICATION SLOT

The modules use the latest generation of DSP microprocessors, in this way the components are reduced and reliability is increased.

FRAME (Cabinet type) 150 250 400 600
Capacity System (KVA) 50~100 50~150 50~200 50~250 50~300 50~400 50~500 50~600
Module (KVA) 50
Module (KW) 2 3 4 5 6 8 10 12
Maximum Number of Modules 3 5 8 12
Input Phases 3 Phases + Neutral + GND
Rated Voltage 380/400/415Vac
Voltage Range 138~485Vac

◆At 40°C: UPS works at full load when voltage is within 323 and 485 Vac and is derated when voltage is within 323 and 138 Vac.

◆At 30°C: UPS works at full load when voltage is within 305 and 485 Vac and is derated when voltage is within 305 and 138 Vac.

Frequency Range 40Hz-70Hz
Power factor ≥0.99
Bypass Voltage Range ≤3% (100% non-linear load)
Genset input Max voltage: 220V: +25 % (optional +10%, +15%, +20%)

230V: +20 % (optional +10%, +15%)

240V: +15 % (optional +10%)

Min Voltage: -45 % (optional -10%, -20%, -30%)

Frequency protection range: ±10%

Output Phases 3 Phase + Neutral + GND
Rated Voltage 380/400/415Vac (factory setting)
Power factor 1.0
Voltage Regulation ±1%
Frequency ±1%/±2%/±4%/±5%/±10% of rated frequency (optional)
Battery mode frequency (50/60±0.1) Hz
Crest factor 3:1
THD ≤2% linear load
≤4% non-linear load
Battery Voltage Optional Voltage:

±180/192/±204/±216/±228/±240/±252/±264/±276/±288/±300Vdc

(30/32/34/36/38/40/42/44/46/48/50pcs optional)

360Vdc~600Vdc (30~50 pcs, 36 ~50 pcs no derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8)

Load current on each module (A) max. 20A
Transfer time From grid to batteries: 0ms from grid to bypass: 0ms
Protections Overload Inverter overload capacity:

◆ 105% < load ≤ 110%: transfer to bypass mode after 60 min

◆ 110% < load ≤ 125%: transfer to bypass mode after 10 min

◆ 125% < load ≤ 150%: transfer to bypass mode after 1 min

Bypass overload capacity:

◆ Temperature ≤ 30°C, load ≤ 135%: long time

◆ Temperature ≤ 40°C, load ≤ 125%: long time

◆ 1000% load: 100 ms

Short circuit Involves entire system
Overheating Normal Mode: transfer to Bypass,

Battery mode: turn off UPS immediately

Self-diagnosis At start-up and through software
EPO (optional) Switches immediately the unit
Battery Advanced battery management
Noise suppression According to EN62040-2
Communication Interface RS232, RS485, LBS, Parallel, SNMP card (optional), Relay card (optional)
Environment Operating temperature 0°C~40°C
Storage temperature -25°C~55°C
Humidity 0%~95% non-condensing
Altitude < 1500m
Display Acoustic and display Grid Failure, Low Battery, Overload, System Failure
LED UPS Failure, Alarms and Normal Operation
Data Input voltage, input frequency, output voltage, output frequency, load percentage, battery voltage, parameter set, event history…
Various FRAME size

(WxDxH) mm

600x850x1200 600x850x1600 600x850x2000 1200x850x2000
MODULE size

(WxDxH) mm

440x320x130
Cabinet weight (Kg) 145 155 250 265 280 360 480 540
Module weight Kg) 34
Safety standards CE,EN/IEC 62040-3,EN/IEC 62040-1-1