NTL – MODULAR 50/60Hz FREQUENCY CONVERTER THREE PHASE, SINE WAVE, RACK MODULES form 50 to 600KVA

The new NTL range uses the modular 19″ rack drawer technology and was created to guarantee the best quality and reliability of service.

Each power module works in a “decentralized parallel” with the others, and the complete system autonomously divides the input load.

In the event of a failure of one of the modules, it is automatically excluded (decentralized parallel), thus ensuring a seamless power supply with the remaining modules.

Among the strengths of the NTL modular range we have a system efficiency > 95% (high efficiency), a reduction in repair times and service costs of less than 30 ‘and the centralization of the static switching system that gives greater guarantees.

We recommend the use of the NTL series for Data Centers, Banks, Hospitals, Airports, Emergency Lights and any Industrial application.

MAIN FEATURES

  • Input power factor 0.99
  • Harmonic input distortion <2%
  • Centralized control display, which allows you to check at any time, (even by removing a single module) the actual power and data related to all modules.
  • EPO function
  • Display LCD touch screen

COMMUNICATION PORTS:

  • 1x RS232 – 2x Rs485
  • 1x MODBUS PORT
  • 1x CLEAN CONTACTS
  • 2x COMMUNICATION SLOT

The modules use the latest generation of DSP microprocessors, in this way the components are reduced and reliability is increased.

FRAME (Cabinet type) 150 250 400 600
Capacity cabinet (KVA/kW) 50~100 50~150 50~200 50~250 50~300 50~400 50~500 50~600
Module (KW) 50
Standard module 2 3 4 5 6 8 10 12
Max N. of modules 3 5 6 12
Input Phases 3 Phease + Neutral + GND
Rated voltage 380/400/415Vac
Voltage range 138~485Vac
Frequency range 40Hz-70Hz
Power factor ≥0.99
THDi ≤3% (100% carico non lineare)
Uscita Phases 3 Phease + Neutral + GND
Rated voltage 380/400/415Vac (set in the factory)
Power factor 1
Voltage accuracy ±1%
Frequency 50Hz or 60Hz ±1% (set in the factory)
Crest factor 3:1
THD ≤2% linear load
≤4% non linear load
Protection Overload Load ≤110%: 60min, ≤125%: 10min, ≤150%: 1min

≥150% immediate turn off

Short circuit Involves entire system
Overload Immediate turn off
Self diagnosis At start up and via software
EPO (optional) Immediate turn off
Noise suppression According to EN62040-2
Communication interface RS232, RS485, LBS, Parallel, SNMP card (optional), relay card (optional)
Environment Working temperature 0°C~40°C
Warehouse temperature -25°C~55°C
Humidity 0%~95% non condensing
Altitude < 1500m
Display Display + audible alarms Grid fault, overload, Internal fault
LED Fault, alarms and normal operation
Data reading Input voltage, input frequency, output voltage, output frequency, load percentage, set of parameters, events log
Various FRAME Dimensions

(WxDxH) mm

600x850x1200 600x850x1600 600x850x2000 1200x850x2000
MODULE Dimensions

(WxDxH) mm

440x320x130
Cabinet weight (Kg) 145 155 250 265 280 360 480 540
Module Weight (Kg) 34
Standards CE,EN/IEC 62040-3,EN/IEC 62040-1-1