BT – INDUSTRIAL UNINTERRUPTIBLE POWER SUPPLY (UPS) UNITS ON-LINE DOUBLE CONVERSION

The new BT three-phase range joins the current lineups with specific INDUSTRIAL characteristics. Power range in stand-alone systems from 200kVA to 1000kVA. Parallel capability up to 8 units. The main features that distinguish it are technical and structural robustness and latest-generation 3-level technology. This range is recommended for those who have power supply problems with micro-interruptions, mains failures, and grid instability, with a correction of ±20%. In high-power installations, where the main production grid or high-power electrical lines are supplied, from 200kVA to 1MW, equipment failures and production downtime can be avoided, resulting in significant savings that can be classified as Industry 4.0.

Main features:

• Cos-phi 1.0
• Input harmonic distortion ≤ 3%
• System efficiency up to 96%
• Dual power input
• Parallel up to 8 units
• Charging capacity from 80 A to 340 A
• Ability to power inductive and capacitive loads with 100% imbalance
• Standard interfaces: RS232 and 485 Modbus
• Backfeed present

HTML

BT MODEL…… 200 250 300 400 500 600 800 1000
Power (kVA/kW) 200 250 300 400 500 600 800 1000
INPUT
Nominal voltage 380/400/415Vac (3ph+N+PE)
Voltage range 138-305Vac at 40% load; 305-485Vac at 100% load
Frequency range 40:70Hz
Power factor ≥ 0.99
Harmonic distortion (THDi) ≤ 3% (100% linear load)
Bypass voltage range Max. voltage: 220V: +25% (Optional +10%, +15%, +20%)

230V: +20% (Optional +10%, +15%)

240V: +15% (Optional +10%)

Min. voltage: -45% (Optional -10%, -15%, -20%, -30%)

Bypass frequency range Frequency protection range: ±10%
Generator Input Supported
OUTPUT
Nominal voltage 380/400/415Vac (3ph+N+PE)
Power factor 1.0
Voltage regulation ± 1%
Frequency Line mode Synchronizes with input, when input frequency >±10%(±1%/±2%/±4%/±5% optional), output 50/60 (±0.1Hz)
Bat. mode (50/60±0.1%) Hz
Crest factor 3:1
Harmonic distortion (THDv) ≤1% with linear load; ≤3% with non-linear load
Efficiency Up to 96%
BATTERIES
Operating voltage ±180/192/204/216/228/240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/46/48/50pcs, 36pcs default,

36~50pcs output power factor 1.0, 32~34pcs output power factor 0.9, 30pcs output power factor 0.8)

Charging current (A, max) 80 100 100 140 180 200 280 340
SYSTEM FEATURES
Transfer time Mains-Battery: 0ms; Mains-Bypass: 0ms
Overload Inverter mode ≤110% 60min, ≤125% 10min, ≤150% 1min, >150% 1.2s shuts down the inverter
Bypass mode 30℃: 135% for long term; 40℃: 125% for long term; >1000%, 100ms
Overheating Mains Mode: Transfers to Bypass; Battery Mode: Shuts down UPS immediately
Low battery voltage Alarm and shutdown
Self-diagnosis At startup and software control
Backfeed protection Supported
EPO (Optional) Shuts down the UPS immediately
Batteries Battery Management
Noise suppression Compliant with EN62040-3
Acoustic and visual alarms Mains Failure, Low Battery, Overload, System Failure
LED & LCD Display Mains Mode, Bypass Mode, Low Battery, Battery Fault, Overload and UPS Fault
LCD display readout Input, Output, Battery, Command, Setting, Maintenance
Communication interface RS232, RS485, Parallel, LBS, Dry contacts, Relay card (Optional), SNMP card (Optional), Battery temperature sensor (Optional)
ENVIRONMENT
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 0~95% (Non-condensing)
Noise (dB) < 65 < 65 < 68 < 68 < 70 < 70 < 73 < 75
PHYSICAL CHARACTERISTICS
DIMENSIONS WXDXH mm 600x850x2000 1200x850x2000 2000x850x2000
Net weight kg 360 400 480 530 800 890 1450 1600
STANDARDS
Safety IEC/EN 62040-1, IEC/EN 62477-1
EMC IEC/EN 62040-2 (IEC 61000-2-2, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11)