HI-SOL – Single and Three Phase 16kV high isolation protection system HI-SOL Series

Single and Three Phase high isolation protection system HI-SOL Series

Single and three-phase rack wih 16kV isolation transformer
20/40kA type 1-2 surge suppression
Mcb input output protection
Isolation resitance protection
High-low voltage – high current protection
IN A VERY TINY SPACE, YOUR BROADCAST, PROTECTED

SINGLE PHASE MODELS

Model HI-SOL02M HI-SOL03M HI-SOL05M HI-SOL06M HI-SOL08M HI-SOL10M
Type Class I 16KV ISOLATION TRANSFORMER
No. of phases Single phase
Rated input voltage 220-230Vac – 50/60Hz
Rated power 2kVA 3.15kVA 5kVA 6.3kVA 8kVA 10kVA
Screen type Copper earthed screen between the windings
Winding construction Copper / Copper
Rated output voltage 220-230Vac – 50/60Hz
Electric class I
Primary protection MCB 8A MCB 15A MCB 20A MCB 25A MCB 32A MCB 40A
Secondary protection MCB 8A MCB 15A MCB 20A MCB 25A MCB 32A MCB 40A
Input connections 2 x 6 sq.mm. terminals + PE 2 x 10 sq.mm. terminals + PE
Isolation class H
Isolation pri/sec 16kV
Surge suppressor 20kA/40kA x 2 poles
Signals and monitoring Output Digital V-meter / A-meter

Output line ON light

Auxiliary outlet 1 x 10 A Schuko outlet with 10 A protection fuse
Isolation monitoring RI-R22 adjustable isolation tester on board
Cooling AF controlled by thermal contact
Protection IP20
Weight kg 25 30 35 45 60 80
Dimensions mm 19” rack x 4U x depth 350mm 19” rack x 5U x depth 400mm 19” rack x 5U x depth 460mm
Operating conditions Ambient temperature: 5 ÷ 25 °c
Ambient humidity percentage: 30 ÷ 75% RH
Altitude: 0 ÷ 1000m above sea level
Conditions of storage and transport. Ambient temperature: -40 ÷ 70 ° C
Ambient humidity percentage: 10 ÷ 100% RH
Standards CEI EN 61558-2-4

 

THREE PHASE MODELS

Model HI-SOL03T HI-SOL06T HI-SOL08T HI-SOL10T
Type Class I 16KV ISOLATION TRANSFORMER
No. of phases Three phase
Rated input voltage 380-400Vac – 50/60Hz
Rated power 3kVA 6kVA 8kVA 10kVA
Rated input voltage 380-400Vac + N – 50/60Hz
Vector group Dyn11
Screen type Copper earthed screen between the windings
Winding construction Copper / Copper
Electric class I
Primary protection MCB 3 x 4A MCB 3 x 8A MCB 3 x 10A MCB 15A
Secondary protection MCB 3 x 4A MCB 3 x 8A MCB 3 x 10A MCB 15A
Input connections 2 x 6 sq.mm. terminals + PE 2 x 10 sq.mm. terminals + PE
Isolation class H
Isolation pri/sec 16kV
Surge suppressor 20kA/40kA x 3 poles
Signals and monitoring Output Digital V-meter / A-meter

Output line ON light

Auxiliary outlet 1 x 10 A Schuko outlet with 10 A protection fuse
Isolation monitoring RI-R22 adjustable isolation tester on board
Cooling AF controlled by thermal contact
Protection IP20
Weight kg 25 35 60 80
Dimensions mm 19” rack x 5U x depth 460mm
Operating conditions Ambient temperature: 5 ÷ 25 °c
Ambient humidity percentage: 30 ÷ 75% RH
Altitude: 0 ÷ 1000m above sea level
Conditions of storage and transport. Ambient temperature: -40 ÷ 70 ° C
Ambient humidity percentage: 10 ÷ 100% RH
Standards CEI EN 61558-2-4