HI-SOL – Single and Three Phase 16kV high isolation protection system HI-SOL Series
Single and Three Phase high isolation protection system HI-SOL Series
Single and three-phase rack wih 16kV isolation transformer
20/40kA type 1-2 surge suppression
Mcb input output protection
Isolation resitance protection
High-low voltage – high current protection
IN A VERY TINY SPACE, YOUR BROADCAST, PROTECTED
SINGLE PHASE MODELS
| Model | HI-SOL02M | HI-SOL03M | HI-SOL05M | HI-SOL06M | HI-SOL08M | HI-SOL10M |
| Type | Class I 16KV ISOLATION TRANSFORMER | |||||
| No. of phases | Single phase | |||||
| Rated input voltage | 220-230Vac – 50/60Hz | |||||
| Rated power | 2kVA | 3.15kVA | 5kVA | 6.3kVA | 8kVA | 10kVA |
| Screen type | Copper earthed screen between the windings | |||||
| Winding construction | Copper / Copper | |||||
| Rated output voltage | 220-230Vac – 50/60Hz | |||||
| Electric class | I | |||||
| Primary protection | MCB 8A | MCB 15A | MCB 20A | MCB 25A | MCB 32A | MCB 40A |
| Secondary protection | MCB 8A | MCB 15A | MCB 20A | MCB 25A | MCB 32A | MCB 40A |
| Input connections | 2 x 6 sq.mm. terminals + PE | 2 x 10 sq.mm. terminals + PE | ||||
| Isolation class | H | |||||
| Isolation pri/sec | 16kV | |||||
| Surge suppressor | 20kA/40kA x 2 poles | |||||
| Signals and monitoring | Output Digital V-meter / A-meter
Output line ON light |
|||||
| Auxiliary outlet | 1 x 10 A Schuko outlet with 10 A protection fuse | |||||
| Isolation monitoring | RI-R22 adjustable isolation tester on board | |||||
| Cooling | AF controlled by thermal contact | |||||
| Protection | IP20 | |||||
| Weight kg | 25 | 30 | 35 | 45 | 60 | 80 |
| Dimensions mm | 19” rack x 4U x depth 350mm | 19” rack x 5U x depth 400mm | 19” rack x 5U x depth 460mm | |||
| Operating conditions | Ambient temperature: 5 ÷ 25 °c | |||||
| Ambient humidity percentage: 30 ÷ 75% RH | ||||||
| Altitude: 0 ÷ 1000m above sea level | ||||||
| Conditions of storage and transport. | Ambient temperature: -40 ÷ 70 ° C | |||||
| Ambient humidity percentage: 10 ÷ 100% RH | ||||||
| Standards | CEI EN 61558-2-4 | |||||
THREE PHASE MODELS
| Model | HI-SOL03T | HI-SOL06T | HI-SOL08T | HI-SOL10T |
| Type | Class I 16KV ISOLATION TRANSFORMER | |||
| No. of phases | Three phase | |||
| Rated input voltage | 380-400Vac – 50/60Hz | |||
| Rated power | 3kVA | 6kVA | 8kVA | 10kVA |
| Rated input voltage | 380-400Vac + N – 50/60Hz | |||
| Vector group | Dyn11 | |||
| Screen type | Copper earthed screen between the windings | |||
| Winding construction | Copper / Copper | |||
| Electric class | I | |||
| Primary protection | MCB 3 x 4A | MCB 3 x 8A | MCB 3 x 10A | MCB 15A |
| Secondary protection | MCB 3 x 4A | MCB 3 x 8A | MCB 3 x 10A | MCB 15A |
| Input connections | 2 x 6 sq.mm. terminals + PE | 2 x 10 sq.mm. terminals + PE | ||
| Isolation class | H | |||
| Isolation pri/sec | 16kV | |||
| Surge suppressor | 20kA/40kA x 3 poles | |||
| Signals and monitoring | Output Digital V-meter / A-meter
Output line ON light |
|||
| Auxiliary outlet | 1 x 10 A Schuko outlet with 10 A protection fuse | |||
| Isolation monitoring | RI-R22 adjustable isolation tester on board | |||
| Cooling | AF controlled by thermal contact | |||
| Protection | IP20 | |||
| Weight kg | 25 | 35 | 60 | 80 |
| Dimensions mm | 19” rack x 5U x depth 460mm | |||
| Operating conditions | Ambient temperature: 5 ÷ 25 °c | |||
| Ambient humidity percentage: 30 ÷ 75% RH | ||||
| Altitude: 0 ÷ 1000m above sea level | ||||
| Conditions of storage and transport. | Ambient temperature: -40 ÷ 70 ° C | |||
| Ambient humidity percentage: 10 ÷ 100% RH | ||||
| Standards | CEI EN 61558-2-4 | |||