RAS – THREE PHASE REACTANCES (CHOKES) FOR MOTOR STARTING from 5Hp to 200Hp 3 starts/h 5″

THREE PHASE REACTANCES (CHOKES) FOR MOTOR STARTING from 5Hp to 200Hp 3 starts/h 5″three phase reactance for starting motors

Rated voltage 400V
Voltage regulation 30% at full load
Frequency 50/60Hz
Protection IP00
Isolation class H (Ta max 45°C)
Copper windings cl. H
Resin impregnated and tropicalized
Connections on DIN rail terminal blocks up to 50Hp
Connections on isolated brass bolts from 75Hp
Lifting holes/lugs from 150Hp
Applid standards: EN61558-2-13
105°C thermostat in central winding on request
for 4 starts/h 20″ version see RAV range here
schema trasformatore isolamento sicurezza schermo sim-trafoaut
sim-ce
consecutive starts starts/h max starting time
1 3 5″
 drawing of THREE PHASE REACTANCES (CHOKES) FOR MOTOR STARTING from 5Hp to 200Hp 3 starts/h 5"

 

Power Power Code dimensions mm. DWG Weight
KW Hp A B C kg.
3.68 5 RAS004 100 140 40 A 4.4
5.52 7.50 RAS006 100 140 50 A 4.5
7.36 10 RAS007 125 159 50 A 4.6
11.04 15 RAS011 125 159 50 A 4.9
14.72 20 RAS015 125 159 65 A 5.3
22.08 30 RAS022 150 184 55 A 7.5
29.44 40 RAS030 150 184 65 A 7.9
36.80 50 RAS036 150 184 75 A 8.1
44.16 60 RAS045 150 184 85 A 9.9
55.20 75 RAS055 200 236 70 A 16.5
73.60 100 RAS074 200 236 80 A 20.0
92.00 125 RAS092 200 236 90 A 26.0
110.40 150 RAS110 250 296 85 A 32.0
128.80 175 RAS129 250 296 95 A 36.6
147.20 200 RAS147 250 296 105 A 42.0