Skip to content

SRS – RACK 19″/TOWER ONLINE UPS 1 to 3kVA 110V-60Hz DOUBLE CONVERSION, SINE WAVE

SRS – RACK 19″/TOWER ONLINE UPS 1 to 3kVA 110V-60Hz DOUBLE CONVERSION, SINE WAVE

The SRS series is a special product with power from 1kVA to 3kVA.

These UPS can be configured in rack or tower version, are based on double conversion online topology with DSP (Digital Signal Processor) technology and operate with an input/output voltage of 110Vac.

The autonomy in case of mains failure can be increased thanks to the additional battery drawers.

The products are equipped as standard with RS232 communication ports and an RJ45 port. In addition, an intelligent slot is available for the insertion of the SNMP card (optional) and an EPO contact.

The input and output terminals are easily accessible for simple configuration in all industrial environments.

The SRS series is ideal for protecting critical loads that require continuous, high-quality power supply with zero mains/battery transfer time.

MODEL SRS01 SRS02 SRS03
CAPACITY* 1000VA/1000W 2000VA/2000W 3000VA/3000W
INPUT
Voltage Range Low Line Transfer 80VAC/70VAC/60VAC/55VAC ± 5 %

( based on load percentage 100% – 80 % / 80 % – 70 % / 70 – 60 % / 60 % – 0)

Low Line Comeback  87VAC/77VAC/67VAC/62VAC ± 5 %
High Line Transfer  150 VAC ± 5 %
High Line Comeback  145 VAC ± 5 %
Frequency Range 40Hz ~ 70 Hz
Phase Single phase with ground
Power Factor ≧ 0.99 @ full load
THDi ≦ 5% @ 100~130VAC

THDU < 1.6% @ input and full linear load condition

OUTPUT
Output voltage 100/110/115/120/127 VAC
AC Voltage Regulation ± 1% (Batt. Mode)
Frequency Range

(Synchronized Range)

47 ~ 53 Hz or 57 ~ 63 Hz
Frequency Range 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz (Batt. Mode)
Current Crest Ratio 3:1
Harmonic Distortion ≦ 2 % THD (Linear Load) ; 4 % THD (Non-linear Load)
Transfer Time AC Mode to Batt. Mode Zero
Inverter to Bypass < 4 ms
Waveform (Batt. Mode) Pure Sinewave
EFFICIENCY
AC Mode ≧89% @ full charged battery ≧91% @ full charged battery
ECO Mode ≧96% @ full charged battery
Battery Mode ≧88% ≧90%
BATTERY
Battery Type 12V/9AH 12V/9AH 12V/9AH
Numbers 2 4 6
Recharge Time 3 hours recover to 95% capacity for internal battery@ 2A charging current
Charging Current Default: 2A, Max: 8A adjustable
Charging Voltage 27.4 VDC ± 1% 54.7 VDC ± 1% 82.1 VDC ±1%
PHYSICAL
Dimension, D X W X H (mm) 410 x 438 x 88 510 x 438 x 88 630 x 438 x 88
Net Weight (kgs) With battery 11.6 19.5 27.5
Without battery 6.6 9.4 12.4
ENVIRONMENT
Operation Humidity 20-95 % RH @ 0- 40°C (non-condensing)
Noise Level Less than 50dBA @ 1 Meter (With fan speed control)
MANAGEMENT
Smart RS-232 or USB Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix and MAC
Optional SNMP Power management from SNMP manager and web browser

* Derate capacity to 80% of capacity when the output voltage is adjusted to 100VAC, 200VAC or 208VAC. For 100/110/115/120/127VAC system, the output power ratings are different based on different input voltage. Please check output power rating table for the details.

Product specifications are subject to change without further notice.

Output Power Rating Table (only for 100/110/115/120/127 VAC system)

Model name Input rating Output rating
SRS01 110-127Vac, 50/60Hz, 12A, 1Ø 100/110/115/120/125/127Vac, 50/60Hz, 1000VA/1000W, 1Ø, 10A
SRS02 110-127Vac, 50/60Hz, 16A, 1Ø 100/110/115/120/125/127Vac, 50/60Hz, 1Ø

2000VA/2000W (@127Vac input) ;

2000VA/1930W (@125Vac input) ;

2000VA/1850W (@120Vac input) ;

2000VA/1740W (@115Vac input) ;

2000VA/1640W (@110Vac input) ;

2000VA/1500W (@100Vac input)

SRS03 110-127Vac, 50/60Hz, 24A, 1Ø 100/110/115/120/125/127Vac, 50/60Hz, 1Ø

3000VA/3000W (@127Vac input) ;

3000VA/2850W (@125Vac input) ;

3000VA/2740W (@120Vac input) ;

3000VA/2650W (@115Vac input) ;

3000VA/2500W (@110Vac input) ;

3000VA/2300W (@100Vac input)

Download the datasheet for the Battery box here.

WhatsApp
Invia con WhatsApp
GDPR Cookie Consent with Real Cookie Banner