MSN – ONLINE DOUBLE CONVERSION SINE WAVE UPS 1-10KVA

MSN – ONLINE DOUBLE CONVERSION SINE WAVE UPS 1-10KVA

On-line double conversion with Digital Signal Processor (DSP) digital control technology.

Among the main features that make this series of high efficiency there are:

  • High input and output PF
  • Wide Input Tolerance Range (Energy Savings)
  • Eco Mode (Economic operation mode)
  • Flexibility and possibility of parallel
  • Power Backup Protection and Surge Protection
  • Monitoring and Self-diagnosis at every turn-on
  • Cold Start (Cold Start)
  • By-pass output
  • Possibility of autonomous expansion with additional battery boxes
  • USB port
  • Contact EPO
  • Included software
  • Intelligent SNMP Network Card Slot

The MSN series is produced with an LCD display from which you can view the operating parameters (more than 50 entries), and where you can set the base configurations.

The UPS MSN, thanks to its compact size, meets the demand for power in small spaces and is suitable for any type of installation. It is a system with double conversion technology online and is available from 1 kVA to 10 kVA with single phase voltages. It is equipped with integrated maintenance bypass (6Kva and 10Kva), with the ability to increase the autonomy available with additional battery packs. It is available in the standard version without transformer and on request it is possible to add it to an external cabinet.

MSN is the ideal product to protect critical loads that require continuous, high-quality power supply with zero-battery transfer times and provide a fault-tolerant electrical protection network.

The 0.9 power factor combined with Digital Signal Processor (DSP) technology delivers high output power and efficiency to all protected loads.

Total power protection – High dynamics of voltage fluctuation without battery power withdrawal.

Monitoring of operation.

Cold start function.

Low / Exhausted Battery Check.

Multiple Level Alarm Stages

All models come with a USB connector for communication and computer dialogue with USB signals (UPS status, batteries, automatic ignition, automatic rescue, etc.).

Internet connection and protection.

MODEL MSN01 MSN02 MSN03
RATED CAPACITY 1000VA / 900W 2000VA / 1800W 3000VA / 2700W
INPUT Input Single phase and earthing
Voltage range 115±5VAC-295±5VAC
Frequency range 45Hz-55Hz@50HZ/55Hz-65Hz@60HZ
Power factor ≥0.98
ECO range Setting output voltage±20VAC
Bypass range 186VAC-252VAC
THDi ≤7%(100% non linear load)
Connection 1x IEC 1x Terminal L/N + T
OUTPUT Output style Single phase and earthing
Rated voltage 208/220/230/240VAC
Power factor 0.9
Voltage accuracy ±2%
Output

Frequency

Line mode 1. When input frequency is in the range,the output frequency is the same as that of input.

When input frequency is out of the range,the output frequency is (50/60±0.2)Hz when turn to battery mode

Battery mode (50/60±0.2)Hz
Crest factor 3:1
Transfer time Mains ←→ Battery = 0ms
Overload capacity Battery mode 108%±5%<load≤150%±5%   >30s   cut off output and warn,

150%±5%<load<200%±5% > 300ms  cut off output and warn

Line mode 108%±5%<load≤150%±5%  > 30s  transfer to bypass and warn

150%±5%<load<200%±5%  >300ms  transfer to bypass and warn

Efficiency Line mode Full load ≥88%
Battery mode Full load ≥85%
ECO Full load ≥94%
Output voltage distortion ≤3% (100% linear load)
≤5% (100% non linear load)
Connection 2x IEC

1x Schuko

6x IEC

1x Schuko – 1x Terminal L/N + T

BATTERY Input battery voltage 24VDC 48VDC 72VDC
Internal battery capacity 2 4 6
Internal battery type 12V/7AH sealed lead acid maintenance free battery

(only refers to standard UPS)

Backup time Full load ≥4min (only refers to standard UPS), as for long backup UPS, the backup time is determined by the capacity of battery.
Charging current (A) 1
  • Our products are manufactured according to the following EMC international grade standard and has passed the CE authentication:

 

MSN01 – 02 – 03
IEC/EN 62040-1
IEC/EN 62040-2
IEC/EN 62040-3
IEC/EN 60950-1
EN50171

 

  • Work Environment

 

MODEL MSN01 – 02 – 03
Temperature 0°C~40°C
Relative humidity 0~95% non condensing
Altitude <1500m

If >1500m, a derating is required

Storage temperature -25°C~55°C
Noise level < 50dB @ 1m.

 

 

  • Mechanical Specification

 

MODEL DIMENSION WxDxH (mm) GROSS / NET WEIGHT (Kg)
MSN01 144x368x215 10,5 / 9,7
MSN02 191x469x339 21,6 / 20
MSN03 26,2 / 24,6

 

  • Items supplied with the product

 

MODEL MSN01 MSN02 MSN03
Instruction manual QR CODE
Software (CD-ROM) Available for download
RS232 cable 1
USB cable 1
Input cable (IEC) 1 1 NO
Output cable (IEC) 2 3 3

 

TYPE MSN06 MSN10
Rated power 6kVA 10kVA
Capacity 5.4 KW 9 KW
AC INPUT Input Single phase & Ground
Power factor ≥ 0.8 (input THDV ≤1%)
Rated voltage 220VAC / 230VAC / 240VAC
Rated frequency 50Hz/60Hz Automatically selected
Voltage range 120~276Vac
Frequency range 45~66Hz
Bypass voltage range 220Vac max:default +25% (+10% ,+15%,20% , 25%)

230Vac max:default +20% (+10% ,+15%,20% )

240Vac max:default +15% (+10% ,+15%)

min:default-45%(-20%, -30% , -45%, )
Bypass frequency range ±1%、±2%、±4%、±5%、±10%
THDI ≤3% (100% liner load,input THDV ≤1%)
≤5% (100% non liner load,input THDV ≤1%)
BATTERY Battery number 16 STANDARD 18/20 Pcs. Can be set
Battery type 12V/7Ah 12V/9Ah
VRLA
Charge model Boost charge or float charge auto switch
Charge time Boost charge up to 20Hr (Max)
Charge current (Max) 1A (Standard)
AC OUTPUT Output type Single phase & Ground
Voltage regulation ±1.0%
Voltage distortion(THD) less than 2% at 100% liner load
less than 5% at 100% non-liner load
Rated voltage 220V/230V/ 240Vac  can be set
Frequency regulation ±0.1% (stand alone)
±0.25% (parallel operation)
Frequency Utility mode:tracking mains frequency
Battery mode:50Hz/60Hz
Frequency track speed 1Hz/s (stand alone)
0.5Hz/s (parallel operation)
Load capacity

(Mains, drop a level in battery mode)

105 %~ 110 %,lasts 1 hour
110%~125%,lasts 10 minutes
125%~150%, lasts 1 minute
>150%,switch to bypass immediately
Overload for bypass >95%, can not inverter-fed
Load for a long time when rated output current under 125%
Bypass load capacity is controlled by bypass circuit breaker, tripping when circuit breaker operating current.
Crest factor 3:1
Efficiency Line Mode Full Load ≥90%
Battery Mode Full Load ≥88%
ECO Full Load ≥96%
Dynamic respond ± 5.0% (100% balance load)
≤5% in a cycle
Inverter output current limit When current instantaneous value is 2 ~ 3 times of rated current peaks (1.414 * rated power/(3 * 220)), the inverter will be conducted in each pulse current limit protection.
DC component ≤200Mv
Switch time Between Normal and battery mode 0ms
Between inverter and bypass 0ms
Noise <55dB (1m)
Display LED+LCD
Safety Meeting IEC62040-1, GB4943
EMI Conduction :IEC 62040-2
Radiation :IEC 62040-2
Harmonics :IEC 62040-2
EMS IEC 62040-2
Isolation resistance > 2MΩ(500Vdc)
Isolation intension 2820Vdc, <3.5mA,1min
Surge Meeting IEC60664-1 1.2/50uS+8/20uS 6kV/3kA.
Protection

IP20

Work Environment

TYPE MSN06 MSN10
Temperature 0°C~40°C
Relative humidity 0~95% non-condensing
Altitude <1500m when>1500m, lower the rated power for use
Handling

On wheels

Mechanical Specification

TYPE MSN06 MSN10
Height (mm) 616
Width (mm) 250
Depth (mm) 502
Net weight (Kg) (standard range) 62 64
Colour Black

Box content

TYPE MSN06 MSN10
User Manual QR CODE
Software (CD-ROM) Available for download
RS232 Cable 1
USB Cable 1
EPO Connector 1

 

APPLIED STANDARDS
IEC/EN 62040-1
IEC/EN 62040-2
IEC/EN 62040-3
IEC/EN 60950-1
EN50171

Download the UPSilon2000 SOFTWARE here.