Skip to content

IMP – SINGLE AND THREE PHASE ELECTRONIC VOLTAGE STABILIZER, OPEN TYPE IP00

SINGLE AND THREE PHASE ELECTRONIC VOLTAGE STABILIZER, OPEN TYPE IP00

The range of IMP electronic voltage STABILIZERS has been extended to include an OPEN IP00 version, which can be integrated into existing systems or into complex electrical panels for which a separate element would not be an adequate solution.

For this reason it is possible to create, on request, both single-phase and three-phase electronic stabilizers, in open structures with fixing holes that allow installation inside electrical panels.

The display, an essential element of the IMP operating logic, is still installed even if not visible, or can be supplied to be installed on the external panel and connected to the open system via flat cable.

Usually no protections are provided, but both input and/or output circuit breaker protection and the classic over-under voltage and over-current protection via contactor may be required.

Since these are units to be integrated and therefore usually without operating elements, the bypass is usually automatic and managed by the system logic, but the possibility of manual control can also be considered.

The other characteristics of the open stabilizers correspond to those of the standard products in their stand-alone version.

  • Safe use with any type of load
  • Microprocessor control and protection unit
  • Input voltage range ±10% or ±15% or -25%+15% or others on request
  • Adjustment speed 500V/sec
  • Static control with modular thyristor design and SMPS technology – high efficiency, absolute quietness
  • LCD front panel
  • Maintenance-free product is not damaged by dust, moisture or vibration.
  • In the event of a fault, automatic disabling and automatic by-pass allow direct operation of the utility from the network; Double changeover contactor for high/low voltage, overcurrent and for start-up delay.
  • Manufactured with the highest quality components to prevent risk of failure
  • Options available on select models: Improved accuracy (±0.5%, ±1%, ±2% depending on models), output circuit breaker, isolation transformer.
  • Manufactured in an ISO-9001:2015 Quality Management System certified factory
Specification
Rated power from 3 to 100KVA
Power factor 1.0
Input voltage 230V AC single-phase 1P + N (115V or other versions available on request)

400Vac three phase 3P+N (230V or other versions available on request)

Input voltage variation standard versions

Optional versions on request

207V to 253V (-10%+10%) / 360V to 440V (-10%+10%)

input range ±15%, -25%+15% or others on request

Input Frequency 50/60Hz ± 5%
Output voltage 230V AC Single Phase / 400V AC + N three phase
Available output current based on power output
Output voltage accuracy Standard ±2% (or ±3% or ±1% depending on input range)

Based on available input range, accuracy option ±1% or ±0.5%)

Regulation thyristor
Adjustment speed 500V/sec. (2/1000 sec/V)
Efficiency at full load > 97%
Max Harmonic Distortion 3%
Permissible load variation 0 to 100%
Permissible overload 3′ to 110-125% of load
  10″ at 126-150% load
  0.2″ Over 151% of load
Room temperature -10°C to +40°C
Relative humidity Up to 90% non-condensing
Altitude up to 1000m without derating
Ventilation A.F. (to be installed into the switchboard containing the product)
Noise Level < 30dB(A) at 1m. 100% load
Frame color RAL7035

Protections:                                                                                                                                                                                                       

  • Automatic bypass with output contactor for high/low voltage or overload
  • Over-temperature alarm
  • Optional Circuit Breaker Input

Display Indications:                                                                                                                                                                                           

Input voltage Output voltage Output frequency
Load Percentage Over-temperature warning Out-of-range voltage warning
Fault Events Log Technical Service Information

Single-phase models

Item Number Rated Power KVA Current rating Dimensions W x D x H cm. Weight KG.
IMP103-XXX 3 13 A on request * on request *
IMP105-XXX 5 22 A on request * on request *
IMP107-XXX 7.5 32 A on request * on request *
IMP110-XXX 10 43 A on request * on request *
IMP115-XXX 15 65 A on request * on request *
IMP120-XXX 20 87 A on request * on request *
IMP130-XXX 30 130 A on request * on request *
IMP140-XXX 40 174 A on request * on request *
IMP150-XXX 50 217 A on request * on request *
IMP160-XXX 60 260 A on request * on request *
IMP180-XXX 80 348 A on request * on request *
IMP1100-XXX 100 430 A on request * on request *

* Dimensions may vary based on component availability and cost at the time of manufacture

Three-phase models

Item Number Rated Power KVA Current rating Dimensions W x D x H cm. Weight KG.
IMP305-XXX 5 7 A on request * on request *
IMP310-XXX 10 14 A on request * on request *
IMP315-XXX 15 21 A on request * on request *
IMP322-XXX 22 28 A on request * on request *
IMP330-XXX 30 43 A on request * on request *
IMP345-XXX 45 65 A on request * on request *
IMP360-XXX 60 87 A on request * on request *
IMP375-XXX 75 108 A on request * on request *
IMP3100-XXX 100 144 A on request * on request *
IMP3120-XXX 120 173 A on request * on request *
IMP3150-XXX 150 217 A on request * on request *

* Dimensions may vary based on component availability and cost at the time of manufacture